High-speed Counter Detailed Settings
Item
Use high
Counter setting
speed
counter 0 to
3.
Counting Mode
Ring Counter
Max. Value
Reset Method
Comparing After
Counter Reset
Pulse Input Mode
Note The power supply must be restarted after the PLC Setup is transferred in order to enable the high-speed
counter settings.
CJ2M CPU Unit Pulse I/O Module User's Manual
Select one of the following.
• Do not use
• Input pulse frequency (60 kHz max.)*
• Input pulse frequency (100 kHz max.)*
* The frequency of the noise filter will change.
Select one of the following.
• Linear mode
• Ring mode
If a ring counter is selected, set the maximum ring count to between 0 and
4,294,967,295 decimal. (The ring counter maximum value will be
4,294,967,295 if 0 is set.)
Select one of the following.
• Z phase, software reset
• Software reset
Select one of the following.
• Stop
• Continue
Select one of the following.
• Differential Phase
• Pulse + Direction
• Up/Down pulse
• Increment pulse
7 High-speed Counters
Setting
7
7-5