Omron SYSMAC CJ Series User Manual page 157

Sysmac cj series cpu unit pulse i/o module
Hide thumbs Also See for SYSMAC CJ Series:
Table of Contents

Advertisement

When the present value of the high-speed counter matches target value 2 (3,500), interrupt task 144
is executed.
Interrupt task
number 144
DM Area Settings
The comparison table for the CTBL(882) (REGISTER COMPARISON TABLE) instruction is set in
D600 through D606.
Word
D600
D601
D602
D603
D604
D605
D606
CJ2M CPU Unit Pulse I/O Module User's Manual
P_On
Value
Description
0002
Number of target values: 2
0BB8
Target value 1: 3,000 (BB8 hex)
0000
008F
Target value 1: Interrupt task No.143
0DAC
Target value 2: 3,500 (0DAC hex)
0000
0090
Target value 2: Interrupt task No. 144
7 High-speed Counters
RSET
Motor operation
reset.
2961.00
RSET
Motor low speed
reset
2961.01
SET
Turns ON motor stop
output.
W0.02
7