Veichi AC10 Series Technical Manual page 96

Advertisement

Function Table
F13.18
(0x0D12)
Switching deviation low value
RUN
F13.19
(0x0D13)
Switching deviation high value
RUN
F13.20
(0x0D14)
Reserved
RUN
F13.21
(0x0D15)
Differential limiting
RUN
F13.22
(0x0D16)
PID output upper limit
RUN
F13.23
(0x0D17)
PID output lower limit
RUN
F13.24
(0x0D18)
PID output filtering time
RUN
F13.25-F13.28: PID feedback disconnection judgment
Parameter
(address)
Name
djustable attribute
F13.25
Feedback disconnection action
(0x0D19)
selection
STOP
F13.26
Feedback
(0x0D1A)
detection time
RUN
F13.27
(0x0D1B)
Wire break alarm upper limit
RUN
F13.28
(0x0D1C)
Wire break alarm lower limit
RUN
F13.29-F13.33: PID dormancy function
Parameter
(address)
Name
djustable attribute
F13.29
(0x0D1D)
Sleep selection
RUN
F13.30
Sleep frequency
(0x0D1E)
RUN
F13.31
(0x0D1F)
Sleep delay
RUN
F13.32
(0x0D20)
Wake up deviation
RUN
F13.33
(0x0D21)
Wake-up delay
RUN
AC10 Series Frequency Inverter Technical Manual
2: Switch according to the deviation
V/F SVC
When the PID deviation is less than this value, the gain 1 parameter
is used.
V/F SVC
When the PID deviation is greater than this value, the gain 2
parameter is used.
V/F SVC
V/F SVC
V/F SVC
V/F SVC
V/F SVC
Content
V/F SVC
0: Continue PID operation without reporting failure
1: Stop and report failure
2: Continue PID operation and output alarm signal
3: Run at the current frequency, output alarm signal
disconnection
V/F SVC
V/F SVC
V/F SVC
Content
V/F SVC
0: Off
1: Valid
V/F SVC
V/F SVC
V/F SVC
V/F SVC
92
20.0%
(0.0~100.0%)
80.0%
(0.0~100.0%
5.0%
(0.0~100.0%)
100.0%
(0.0~100.0%)
0.0%
(-100.0~Fb.19)
0.000s
(0.000~6.000s)
Factory default
(setting range)
0
(0 ~ 3)
1.0s
(0.0~120.0s)
100.0
(0.0~100.0%)
0.0%
(0.0~100.0%)
Factory default
(setting range)
0
(0 ~ 1)
10.00Hz
(0.00~50.00Hz)
60.0S
(0.0~3600.0S)
5.0%
(0.0~50.0%)
1.0S
(0.0~60.0S)