Parameter details
F01.20
Acceleration/deceleratio
(0x0114)
n
time
STOP
frequency
0: maximum frequency
the reference for the acceleration/deceleration time is F01.10 [maximum frequency].
1: fixed frequency
the reference for the acceleration/deceleration time is a fixed frequency of 50.00 Hz.
2: Set the frequency
the reference of the acceleration/deceleration time is the set frequency. If the set frequency changes frequently, the acceleration
of the motor changes, so pay attention to the application.
F01.21: Acceleration/deceleration time range selection
Code
Name
(Addr.)
F01.21
Acceleration/deceleratio
(0x0115)
n time range selection
STOP
Note: The default value is 2, which is two decimal places.
0: no decimal point
1:1 decimal point
2: 2 decimal places
F01.22: Acceleration time 1
Code
Name
(Addr.)
F01.22
(0x0116)
Acceleration time 1
RUN
Code
Name
(Addr.)
F01.23
(0x0117)
Deceleration time 1
RUN
The relationship between the default value of the acceleration/deceleration time and the drive power level is as follows.
Drive power
<=22KW
<=45KW
<=55KW
<=75KW
<=90KW
<=132KW
<=160KW
<=185KW
<=220KW
Others
Code (Addr.)
Name
F01.24
(0x0118)
Acceleration time 2
RUN
F01.25
(0x0119)
Deceleration time 2
RUN
Code (Addr.)
Name
F01.26
(0x011A)
Acceleration time 3
RUN
F01.27
(0x011B)
Deceleration time 3
RUN
AC10 Series Frequency Inverter Technical Manual
V/F SVC
reference
Set the acceleration/deceleration time reference frequency
Content
V/F SVC
Set the decimal point of the F01.22 ~ F01.29 [Acceleration / deceleration
time 1~4] parameter
Content
V/F SVC
Set the value of acceleration time 1
Content
V/F SVC
Set the value of deceleration time 1
Default value of acceleration/deceleration time 1~4
6.00s
12.00s
18.00s
24.00s
30.00s
36.00s
42.00s
48.00s
54.00s
60.00s
Content
V/F SVC
Set the value of acceleration time 2
V/F SVC
Set the value of deceleration time 2
Content
V/F SVC
Set the value of acceleration time 3
V/F SVC
Set the value of deceleration time 3
110
0
(0 ~ 3)
Factory setting
(Setting range)
2
(0 ~2)
Factory setting
(Setting range)
With power level
(Change with F01.21)
Factory setting
(Setting range)
With power level
(Change with F01.21)
Factory setting
(Setting range)
With power level
(Change with F01.21)
With power level
(Change with F01.21)
Factory setting
(Setting range)
With power level
(Change with F01.21)
With power level
(Change with F01.21)

Advertisement

loading

This manual is also suitable for:

Sis series