Parameter details
AI linear processing diagram
Table 11.2 Selection of AI Input Application
Parameter code
F01.02
F01.04
F01.08
F01.11
F03.41
F03.54
F03.55
F13.00
F13.03
F05.6x group: AI curve 1 processing
The set values of curve 1 F05.60, F05.62, F05.64, F05.66 must be set incrementally.
The set values of curve 2 F05.70, F05.72, F05.74, F05.76 must be set incrementally.
Curve 1 and curve 2 can set two inflection points, which are divided into three straight lines. The slope of each segment can be different, which can achieve
a more flexible correspondence, as shown in the following figure:
Code (Addr.)
Name
F05.60
(0x053C)
Curve 1 lower limit
RUN
F05.61
Curve 1 lower limit
(0x053D)
corresponding setting
RUN
F05.62
Curve 1 inflection point
(0x053E)
1
RUN
AC10 Series Frequency Inverter Technical Manual
Linear processing output
0
lower limit
Name
Frequency given channel A
Frequency given channel B
Run command to bind a given frequency
channel
Upper frequency source selection
Torque command given
Torque control forward speed limit selection
Torque control reverse speed limit selection
PID controller given signal source
PID controller feedback signal source
Curve processing output
Inflection
Inflection
0
lower limit
point 1
point 2
Content
V/F SVC
When the AI input value is less than this value, it is processed according to
the value
Set the percentage of the set value corresponding to the lower limit of curve
1
V/F SVC
Set the value of curve 1 inflection point 1
Upper limit
corresponding setting
Lower limit
corresponding setting
Upper limit
Linear processing input
Upper limit
corresponding setting
Inflection point 2
corresponding setting
Inflection point 1
corresponding setting
Lower limit
corresponding setting
Upper limit
Curve processing input
136
Set value
2: AI given
2: AI given
2: AI given
2: AI given
2: AI given
2: AI× F03.56
2: AI× F03.57
2: AI given
2: AI given
Factory setting
(Setting range)
0.0%
(0.0 ~ 100.0%)
0.00%
(0.00 ~ 100.00%)
30.0%
(0.0 ~ 100.0%)