F06.00: AO output mode selection
Code
Name
(Addr.)
F06.00
AO
output
(0x0600)
selection
RUN
0:0~10V mode
1:4.00~20.00mA mode
2: 0.00 to 20.00 mA mode
Note:
F06.00 Selecting a different mode requires dialing the dial switch on the control panel to the corresponding position.
Code
Name
(Addr.)
F06.01
(0x0601)
AO output selection
RUN
Set value
0
Given frequency
1
Output frequency
2
Output current
3
Input voltage
4
The output voltage
5
Mechanical speed
6
Given torque
7
Output torque
8
PID given
9
PID feedback
10
Output Power
11
bus voltage
12
AI input value
13
Reserved
14
Reserved
15
PUL input value
16
Module temperature 1
17
Module temperature 2
18
RS485 given
AO frequency output
Min
AO port pulse frequency output diagram
Content
mode
V/F SVC
Set the form of the analog output signal.
Content
V/F SVC
Set the amount of analog output.
Name
0.00% corresponding value
0.00Hz
0.00Hz
0.00A
0.0V
0.0V
0rpm
0.00% torque
0.00% torque
0.00% PID given
0.00% PID feedback
0Kw
0V
AI input lower limit
Reserved
PUL input lower limit
0 degrees Celsius
0 degrees Celsius
0
139
AO frequency output
upper limit
AO frequency
output lower limit
Monitoring
Max
amount
100.00% corresponding value
Maximum frequency
Maximum frequency
2 times rated current of the drive
2 times rated voltage of the drive
Rated voltage of the drive
The speed corresponding to the maximum
frequency
200% torque
200% torque
100% PID given
100% PID feedback
Rated output power
2 times rated DC voltage of the drive
AI input upper limit
Reserved
PUL input upper limit
100 degrees Celsius
100 degrees Celsius
1000
AC10 Series Frequency Inverter Technical Manual
Parameter details
Factory setting
(Setting range)
0
(0 ~ 2)
Factory setting
(Setting range)
0
(0 ~ 19)