Wiring of PNP characteristic transistors
Uses internal 24V power supply
Wiring of NPN characteristic transistors
Uses internal 24V power supply
(default short connection)
Note:
7.5KW and above with NPN and PNP functions similar to AC310
Auxiliary Terminal Output Capability
Terminal
Function definition
+10V
10V auxiliary power supply output, constitutes loop with GND.
AO
Analog monitor output, constitutes loop with GND.
+24V
24V auxiliary power supply output, constitutes loop with COM.
Collector open circuit output, can set the action-object by
Y
program.
TA/TB/TC
Passive connector output, can set the action-object by program.
Function Specification of Switch Terminals
AC10
+24V
PLC
COM
X1
X2
X3
X4
Shielded cable
E
AC10
Jumper Caps
+24V
PLC
X1
X2
X3
X4
COM
Shielded cable
E
Uses external 24V power supply
External 24V power
Jumper Caps
+24V
PLC
COM
Shielded cable
Uses external 24V power supply
+24V
PLC
COM
Shielded cable
Note:Remove the jumpers at the +24V and
PLC terminals for external 24V power supply.
Max output
50mA
As frequency,voltage signal, max output 2mA
100mA
DC24V/50mA
3A/240VAC
15
Installation and Wiring
AC10
+24V
Jumper Caps
PLC
COM
X1
X2
X3
X4
E
AC10
Jumper Caps
External 24V power
+24V
PLC
-
+
X1
X2
X3
X4
COM
E
AC10 Series Frequency Inverter Technical Manual
+24V
PLC
COM
+24V
PLC
COM

Advertisement