Download Print this page

Veichi AC10 Series Technical Manual page 181

Advertisement

Code (Addr.)
Name
F13.04
Feedback signal low
(0x0D04)
pass filtering time
RUN
Feedback signal filtering time: used to filter the feedback signal, which can reduce the influence of the feedback amount. The longer the filtering time,
the stronger the anti-interference ability, but the reaction speed becomes slower.
Code (Addr.)
Name
F13.05
(0x0D05)
Feedback signal gain
RUN
Feedback signal gain: for linear proportional adjustment of the feedback input signal
F13.06: Feedback signal range
Code (Addr.)
Name
F13.06
(0x0D06)
Feedback signal range
RUN
Feedback signal range: The PID feedback signal range is a dimensionless unit used to adjust the PID feedback display.
F13.07-13.24: PID adjustment
Code (Addr.)
Name
F13.07
(0x0D07)
PID control selection
RUN
Unit position: feedback feature selection
0: Positive characteristic Applicable when the PID feedback amount is greater than the PID given amount, it is required to reduce the drive output frequency
to maintain the PID balance; such as constant pressure water supply, gas supply, winding tension control, etc.
1: Negative characteristic Applicable when the PID feedback amount is greater than the PID given amount, the drive output frequency is required to rise
to maintain the PID balance; such as the central air conditioning thermostat control, unwinding tension control.
Ten: reserved
Hundreds: reserved
Thousands: differential adjustment properties
0: Differentiate the deviation
1: Differentiate the feedback
Code (Addr.)
Name
F13.08
(0x0D08)
PID preset output
RUN
Code (Addr.)
Name
F13.09
PID
preset
(0x0D09)
running time
RUN
This function is defined as the PID running after the start, the output is first preset according to the PID preset output [F13.08], and the time set by the PID
preset output running time [F13.09] is continuously run on the output value. PID closed loop characteristic operation.
Hint: When PID is used for frequency reference [F01.02=8] preset output 100% corresponds to maximum frequency output.
Code (Addr.)
Name
F13.10
PID control deviation
(0x0D0A)
limit
RUN
The PID feedback amount is the maximum deviation allowed for the PID given; when the feedback amount is within this range, the PID adjustment stops
and the output remains unchanged; the reasonable use of this function helps to coordinate the accuracy and stability of the system output. contradiction.
Content
V/F SVC
Used to set the feedback signal low pass filter time
Content
V/F SVC
Used to set the feedback signal gain
Content
V/F SVC
Used to set the feedback signal range
Content
V/F SVC
Content
V/F SVC
Used to set the PID preset output
Content
output
V/F SVC
Used to set the PID preset output running time
Content
V/F SVC
Used to set the PID control deviation limit
177
Parameter details
Factory setting
(Setting range)
0.010
(0.000~6.000)
Factory setting
(Setting range)
1.00
(0.00~10.00)
Factory setting
(Setting range)
100.0
(0.0~100.0)
Factory setting
(Setting range)
0100
(0000~1111)
Factory setting
(Setting range)
100.0%
(0.0~100.0%)
Factory setting
(Setting range)
0.0s
(0.0~6500.0s)
Factory setting
(Setting range)
0.0%
(0.0~100.0%)