Download Print this page

Veichi AC10 Series Technical Manual page 138

Advertisement

Parameter details
Schematic diagram of linear processing of PUL input frequency
Note:
The decimal point of F05.31 and F05.33 parameter values is determined by the setting value of F05.30.
After PUL is linearly processed, the output value range is F05.32~F05.34. If F01.02 = 5 [frequency given channel A = PUL given], then 100.00%
corresponds to the maximum frequency, 0.00% corresponds to 0.00Hz, 0.00% Linear processing between ~100.00%
The choice of PUL input:
Table 11.2 Selection of PUL Input Applications
Parameter code
F01.02
F01.04
F01.08
F01.11
F03.41
F03.54
F03.55
F13.00
F13.03
Code
Name
(Addr.)
F05.35
(0x0523)
PUL filter time
RUN
Note:
The longer the filtering time, the stronger the anti-interference ability, but the reaction speed becomes slower.
Code (Addr.)
Name
F05.36
(0x0524)
PUL cutoff frequency
RUN
Note:
The smaller the value is set, the lower the pulse frequency that the PUL port can receive, but when the PUL port pulse frequency disappears, the
drive determines that the pulse input is "0 Hz" for a longer period of time.
The PUL input signal is first judged by the cutoff frequency, then subjected to PUL linear processing, and finally filtered.
F05.4x group: analog (AI) input characteristic selection
There are two analog AI inputs in the drive. The input source can be divided into voltage input range of 0~10.0V, current input range is 0~20mA, and the
matching input source is selected by the DIP switch on the control board according to different signal sources. The factory default dial switch dials the
voltage input.
1: AI input signal type
AC10 Series Frequency Inverter Technical Manual
Linear processing output
0
lower limit
Name
Frequency given channel A
Frequency given channel B
Run command to bind a given frequency
channel
Upper frequency source selection
Torque command given channel
Torque control forward speed limit selection
Torque control reverse speed limit selection
PID controller given signal source
PID controller feedback signal source
Content
V/F SVC
Set the filter time of the input pulse signal
Content
V/F SVC
PUL port minimum recognition pulse frequency, lower than the pulse
frequency of this parameter, the drive no longer recognizes, according to
the "0Hz" frequency value processing
Upper limit
corresponding setting
Lower limit
corresponding setting
Upper limit
Linear processing input
134
Set value
5: PUL given
5: PUL given
6: PUL given
5: PUL given
5: PUL given
5: PUL× F03.56
5: PUL× F03.57
5: PUL given
5: PUL given
Factory setting
(Setting range)
0.100s
(0 ~ 9.000s)
Factory setting
(Setting range)
0
(0 ~ 2)