F10.35
(0x0A23)
Load warning detection level 2
STOP
F10.36
(0x0A24)
Load warning detection time 2
STOP
F10.4x group: Stall protection
Parameter
(address)
Name
djustable
attribute
F10.40
Too large peed deviation protection
(0x0A28)
action
STOP
F10.41
Speed deviation excessive detection
(0x0A29)
threshold
STOP
F10.42
(0x0A2A)
Speed deviation too large detection time
STOP
F10.43
(0x0A2B)
Speed protection action
STOP
F10.44
(0x0A2C)
Rapid detection threshold
STOP
F10.45
(0x0A2D)
Rapid speed detection time
STOP
F10.5x group: Fault recovery protection
Parameter
(address)
Name
djustable
attribute
F10.50
(0x0A32)
Failure self-recovery
STOP
V/F SVC
Set the detection value of load warning 2
When VF is controlled, this value is 100% corresponding to the
rated current of the motor.
When vector control, this value corresponds to 100% of the rated
output torque of the motor.
V/F SVC
Set the duration of the detected load warning 2, the load is
greater than the load warning detection level and continue for
that time, and the load warning is detected 2
Content
V/F SVC
Set the warning detection mode selection and alarm mode
selection when the motor reference speed and feedback speed
deviation are too large
LED "0" digit: Check out options
0: No detection
1: Only at constant speed detection
2: Always testing
LED "00" digit: Alarm selection
0: Free stop and report failure
1: Alarm and continue to run
V/F SVC
Set the detected value whose speed deviation is too large. This
value corresponds to F01.10 [maximum frequency].
V/F SVC
Set the duration of the detection speed deviation too large, the
deviation of the given speed and feedback speed is greater than
F10.41 and continues to be like that, an early warning of
excessive speed deviation is detected.
V/F SVC
Set the alarm detection mode selection and alarm mode
selection when the motor is rotating too fast
LED "0" digit: check out options
0: No detection
1: Only at constant speed detection
2: Always testing
LED "00" digit: Alarm selection
0: Free stop and report failure
1: Alarm and continue to run
V/F SVC
Set the detection value of the fast warning, which corresponds to
F01.10 [maximum frequency]
V/F SVC
Set the duration of the detection of the rotating speed, the
feedback speed is greater than F10.44 and continues like that,
and the speed warning is detected.
Content
V/F SVC
Set the number of fault self-recovery that is allowed to be
performed.
Note: A value of 0 indicates that the fault self-recovery function
85
130.0%
(0 ~200.0%)
5.0s
(0 ~60.0)
Factory default
(setting range)
00
(00 ~12)
10.0%
(0 ~60.0%)
2s
(0 ~60)
00
(00 ~12)
110.0%
(0 ~150.0%)
0.01s
(0 ~2)
Factory default
(setting range)
0
(0 ~10)
AC10 Series Frequency Inverter Technical Manual