Increase the detection delay of terminal X2, and enhance the filtering effect on the input terminal signal.
F05.14~F05.15: Terminal X3 detection delay
Code (Addr.)
Name
F05.14
X3 effective detection
(0x050E)
delay
RUN
F05.15
X3 uneffective check
(0x050F)
delay
RUN
Note:
Increase the detection delay of terminal X3, and enhance the filtering effect on the input terminal signal.
Code (Addr.)
Name
F05.16
X4 effective detection
(0x0510)
delay
RUN
F05.17
X4 uneffective check
(0x0511)
delay
RUN
Note:
Increase the detection delay of terminal X4 and enhance the filtering effect on the input terminal signal.
F05.2x group: Digital input terminal action selection
F05.20: Terminal control operation mode
Code (Addr.)
Name
F05.20
(0x0514)
Terminal control mode
STOP
0: Two-wire control 1
The operation is in one direction. This mode is the most commonly used two-wire mode. The factory default is to determine the forward and reverse running
of the motor by the X1 (forward running) and X2 (reverse running) terminal commands. As shown below:
1: two-wire control 2
The operation is separated from the direction. The forward running terminal X1 (forward running) defined in this mode is the operation enable terminal.
The definition of the direction is determined by the state of the reverse running terminal X2 (reverse running). As shown below:
2: Three-wire control 1
In this mode, the three-wire operation control terminal (Xi) is the stop operation terminal, and the running command is generated by the forward rotation
operation terminal X1 (forward rotation operation), and the direction is controlled by the reverse rotation operation terminal X2 (reverse rotation operation).
The three-wire operation control terminal (Xi) is an effective input.
Content
V/F SVC
Delay time corresponding to the transition of the terminal X1 from the
inactive state to the active state
V/F SVC
Delay time corresponding to the transition of the terminal X1 from the active
state to the inactive state
Content
V/F SVC
Delay time corresponding to the transition of the terminal X1 from the
inactive state to the active state
V/F SVC
Delay time corresponding to the transition of the terminal X1 from the active
state to the inactive state
Content
V/F SVC
Set terminal control mode
131
Parameter details
Factory setting
(Setting range)
0.010s
(0.000 ~ 6.000s)
0.010s
(0.000 ~ 6.000s)
Factory setting
(Setting range)
0.330s
(0.000 ~ 6.000s)
0.330s
(0.000 ~ 6.000s)
Factory setting
(Setting range)
0
(0 ~ 3)
AC10 Series Frequency Inverter Technical Manual