Parameter details
3: Three-wire control 2
In this mode, the three-wire operation control terminal (Xi) is the stop operation terminal, and the operation command is generated by the forward rotation
operation terminal X1 (forward rotation operation) or the reverse rotation operation terminal X2 (reverse rotation operation), and both control the running
direction.
Hint: SB1: Stop button; SB2: Forward run button; SB3: Reverse run button; "Xi" is multi-function input terminal set to "3" [3-wire operation control (Xi)].
Note:
When the set frequency is lower than the starting frequency, the drive will not start, it will be in the standby state, and the running indicator will
light.
Code
Name
(Addr.)
F05.22
X1~X4 terminal characteristics
(0x0516)
selection
RUN
Note: The drive defaults to the terminal closing. If the selection is valid, you need to pay attention to the power-on initialization. When the terminal is
disconnected, the closing signal will be output for a while.
Unit: Terminal X1
0: Closed valid
1: disconnection is valid
Ten places: terminal X2
0: Closed valid
1: disconnection is valid
Hundreds place: terminal X3
0: Closed valid
1: disconnection is valid
Thousands: terminal X4
0: Closed valid
1: disconnection is valid
Code
Name
(Addr.)
F05.25
Terminal adjustment frequency
(0x0517)
mode
STOP
Note: This parameter is valid only when [10: Frequency increment or 11: Frequency decrement] is selected for the multi-function input terminal function.
0: Power down shutdown storage
When the terminal adjustment frequency is incremented or decremented, the frequency record is maintained after the machine is powered off or stopped.
During power-on operation, the frequency converter increases and decreases the frequency from the last stop.
AC10 Series Frequency Inverter Technical Manual
SB1
K1
direction control
0
FWD
1
REV
aracteristics selection
Content
V/F SVC
Select terminal X1~X4 to be closed or open
Content
V/F SVC
Set the way the terminal increments or decrements the frequency
frequency inverter
SB2
X1
run order(run while on)
Xi
stop order(stop while off)
K1
X2
FWD/REV order(run while close)
COM
common input port
2: 3-line 1
132
Factory setting
(Setting range)
0000
(0 ~ 0x1111)
Factory setting
(Setting range)
0
(0 ~ 2)