Code
Name
(Addr.)
F03.34
(0x0322)
Output power limit
RUN
Note: The set value 100.0% corresponds to the rated motor power.
Energy efficient operation
The asynchronous machine vector control is effective. When the energy-saving operation is performed, the output current is automatically reduced by
analyzing the torque output, so that the heating loss of the motor is reduced to achieve the energy saving effect.
F03.37: Energy-saving operation
Code
Name
(Addr.)
F03.37
Energy
(0x0325)
operation
RUN
0: off
1: on
F03.38: Energy-saving operation excitation lower limit
Code
Name
(Addr.)
F03.38
Energy-saving operation
(0x0326)
excitation lower limit
RUN
Note: The set value is 100.0% motor rated excitation.
F03.39: Energy-saving operation filter coefficient
Code
Name
(Addr.)
F03.39
Energy-saving operating
(0x0327)
filter coefficient
RUN
F03.4x-F03.5x Group: Torque Control
Torque command given
F03.40: Torque control selection
Code
Name
(Addr.)
F03.40
(0x0328)
Torque control selection
RUN
0: speed control selection
1: Torque control selection
Note:
F5.0x = 60 [multi-function input terminal = switch to torque control], priority is higher than F03.40 [torque control selection].
F03.41: Torque command given
Code
Name
(Addr.)
F03.41
(0x0329)
Torque command given
RUN
Unit position: torque reference channel A
0: Torque digital reference
1: keyboard potentiometer
2: AI input
3: Reserved
4: Reserved
5: PUL input
6: RS485 communication given (communication address is 0x3005)
Tens place: torque reference channel B
Same as torque reference channel A setting selection
Hundreds: Channel A, B combination
0: torque reference channel A
1: torque reference channel B
2: Torque given the sum of channel A and channel B
Content
SVC
Set output power limit
Content
efficient
SVC
Energy-saving operation function selection
Content
SVC
Set the excitation limit of energy-saving operation
Content
SVC
Set energy saving operation filter coefficient
Content
SVC
Torque control selection
Content
SVC
Set torque command given
119
Parameter details
Factory setting
(Setting range)
250.0%
(0.0 ~ 400.0%)
Factory setting
(Setting range)
0
(0 ~ 1)
Factory setting
(Setting range)
50.0%
(0.0 ~ 80.0%)
Factory setting
(Setting range)
0.010s
(0.000 ~ 6.000s)
Factory setting
(Setting range)
0
(0 ~ 1)
Factory setting
(Setting range)
0x0000
(0x0000 ~ 0x0566)