Veichi AC10 Series Technical Manual page 173

Advertisement

F11.03
Keyboard
(0x0B03)
button settings
STOP
0: Non-keyboard control mode is invalid.
operation signal.
1: Non-keyboard control mode is stopped according to stop mode.
running signal, it can be used as the stop button to stop the drive in the stop mode set by [F07.10].
It can be used as the stop button, and the stop mode is [F07.10] setting mode.
2: Non-keyboard control mode is stopped in free mode.
it can be used as the stop button to stop the drive in the free stop mode.
Can be used as a stop button, the stop mode is free stop.
Note:
If [F11.03] selects 1 or 2, the drive will be in the stop lock state after the keyboard stop button is stopped during terminal control or RS485
control. In this case, if the drive is to be re-run, the stop command must be sent to the selected run command channel to release the lock
state before the drive can run again.
F11.04: Status interface up and down keys (knob) function selection
Code (Addr.)
Name
F11.04
Status interface up and
(0x0B04)
down
keys
STOP
function selection
Single digit: keyboard up and down keys to modify the selection
0: invalid
1: Used to adjust the frequency keyboard. The F01.09 keyboard up and down keys can quickly modify the setting value of the parameter [F01.09].
2: Used to adjust the PID keyboard given F13.01 keyboard up and down keys can quickly modify the setting value of parameter [F13.01]
3: Keyboard up and down keys to modify the parameter number setting Keyboard up and down keys can quickly modify the setting value of the parameter
[Fxx.yy]
Ten place: power down storage
0: frequency is not stored when power is off
1: frequency power down storage
Select whether to change the modified value to the corresponding parameter when the power is off after the parameter is quickly modified by the up and
down keys of the keyboard.
Hundreds: Action Limit
0: adjustable operation stop
1: Adjustable only during operation, stop and keep
2: Adjustable during operation, stop and clear
Thousands: reserved
Note:
Code (Addr.)
Name
F11.05
Up and down keys to
(0x0B05)
quickly change the
RUN
parameter
setting
Keyboard up and down keys quickly modify the parameter number setting:
LED digits ten digits: function parameter number Fxx.yy yy setting 00~99
LED hundred thousand digits: function parameter number Fxx.yy xx setting 00~15
Code (Addr.)
Name
F11.06
Keyboard
command
(0x0B06)
key selection
STOP
LED ones: built-in, external keyboard button commands
(run command, stop/reset command)
0: External priority, when the external is valid, the built-in is invalid.
1: Built-in priority, when the built-in is valid, the external is invalid
2: Both internal and external are valid, the stop/reset command takes precedence; when both forward and reverse are active, the command is invalid.
LED ten: reserved
LED Hundreds: Reserved
LED Thousands: Keyboard Test (Communication Success Rate)
F11.1x group: Status interface cyclic monitoring
STOP
V/F SVC
The keyboard stop button STOP cannot be stopped as a stop button when it is not a keyboard control
When the keyboard stop button STOP is used as the non-keyboard control running signal,
Content
(knob)
V/F SVC
hange the parameter code setting
Content
V/F SVC
code
Content
V/F SVC
When the keyboard stop button STOP is used as the non-keyboard control
169
Parameter details
0
(0 ~ 2)
Factory setting
(Setting range)
0011
(0000~0213)
Factory setting
(Setting range)
0109
(0000~1559)
Factory setting
(Setting range)
0000
(0000~1122)
AC10 Series Frequency Inverter Technical Manual