Flow chart 2
Flow chart 2-bit motor parameter self-tuning process, the effect of controlling the motor for the drive is better, and the motor parameter self-tuning is
required; (Note: be sure to set the motor rated parameters before learning.)
Set F02.07=1, rotate self-
learning, press SET button
to enter auto-tuning state
Self-tuning
failed, motor
parameters are
not updated
Check the cause
of the fault and
re-tune after
troubleshooting
Start
Make sure the power supply is connected
correctly and confirm that the motor is
wired correctly.
Set the F02.01-F02.06 parameter
according to the motor nameplate
No
Motor Loaded?
Press the RUN button to
start auto-tuning
Yes
error occurs
Press the keyboard RUN
button
End of trial running
27
Yes
Set F02.07=2, then static
self-tune, press SET button
to enter auto-tuning state.
No
AC10 Series Frequency Inverter Technical Manual
Basic Operation and Trial Run