Veichi AC10 Series Technical Manual page 166

Advertisement

Parameter details
F10.16
Bus
(0x0A10)
suppression
STOP
Note: Overvoltage suppression is valid for any control method.
When the bus voltage during the running of the drive reaches or falls below F10.17 [bus undervoltage suppression point], the drive will automatically adjust
the operating frequency to suppress the bus voltage drop, thus ensuring that the drive does not trigger E.LU2 due to the low bus voltage. [Undervoltage
fault].
0: off
1: open
Code (Addr.)
Name
Adjustable attribute
F10.17
Bus
(0x0A11)
suppression point
STOP
Note: The factory value of this parameter is determined by the drive model.
When the bus voltage during the running of the drive reaches or falls below F10.17 [bus undervoltage suppression point], the drive will automatically adjust
the operating frequency to suppress the bus voltage drop, thus ensuring that the drive does not trigger E.LU2 due to the low bus voltage. [Undervoltage
fault].
Code (Addr.)
Adjustable
Name
attribute
F10.18
Bus
(0x0A12)
suppression gain
RUN
Adjust F10.18 [Bus Undervoltage Suppression Gain] to adjust the effect of the undervoltage suppression function. When this parameter is set to 0, the
undervoltage suppression function is turned off.
Code (Addr.)
Adjustable
Name
attribute
F10.19
Bus
(0x0A13)
protection point
STOP
This parameter specifies the lower limit voltage allowed by the bus voltage when the drive is working normally. For some occasions where the grid is low,
the undervoltage protection level can be appropriately reduced to ensure the normal operation of the drive.
Note: When the grid voltage is too low, the output torque of the motor will decrease. For constant power loads and constant torque loads, too low grid
voltage will increase the input and output current of the drive, thus reducing the reliability of the drive operation.
F10.2x group: auxiliary protection
Code (Addr.)
Adjustable
Name
attribute
F10.20
Input and output phase
(0x0A14)
loss protection options
STOP
Set whether the input and output phase loss protection functions are enabled.
Unit: Output phase loss protection function selection
0: Off, the output phase loss protection function is invalid.
AC10 Series Frequency Inverter Technical Manual
V/F SVC
When the bus voltage is lower than the undervoltage suppression point,
undervoltage
the operating frequency is automatically adjusted to suppress the bus
voltage from decreasing, preventing the undervoltage fault.
0: off 1: on
Content
V/F SVC
Set the bus voltage value for the trigger undervoltage suppression
undervoltage
function.
Remarks: T3 overvoltage point: 820V (750 ~ 840)
S2 overvoltage point: 400V (360 ~ 410)
Content
undervoltage
V/F SVC
Set the response effect of undervoltage suppression
Content
V/F SVC
The lower limit voltage allowed by the set bus voltage. Below this value,
undervoltage
the drive reports an undervoltage fault.
Remarks: T3 overvoltage point: 820V (750 ~ 840)
S2 overvoltage point: 400V (360 ~ 410)
Content
V/F SVC
Set whether the input and output phase loss protection functions are
enabled.
Unit: Output phase loss protection
0: off 1: on
Ten digits: input phase loss protection
0: off
1: On, detected the input missing phase report warning A.ILF, continue to
run
2: Turn on, detect input missing phase report fault E.ILF, free stop
162
0
(0 ~ 1)
Factory setting
(Setting range)
T3: 430
S2: 240
(T3: 350 ~450
S2: 180 ~260)
同 时 受 过 压 点 限
Factory setting
(Setting range)
100.0%
(0.0~500.0%)
Factory setting
(Setting range)
T3: 320
S2: 190
(T3: 300 ~400
S2: 160 ~240)
Also
subject
to
overpressure limit
Factory setting
(Setting range)
021
(000 ~ 121)