1: Power down is not stored, stop storage
When the terminal adjustment frequency is incremented or decremented, the frequency record is maintained after the machine stops. During the next run,
the frequency converter increases and decreases the frequency from the last stop. Recording is not saved after power failure, starting from 0.00Hz.
2: Run is valid, stop is cleared
When the terminal adjustment frequency is incremented or decremented, the frequency record is not maintained after the machine stops or after power
failure. During the next run, the drive increases and decreases the adjustment from the frequency of 0.00Hz.
F05.26: Terminal UP/DW control frequency increase and decrease rate
Code
Name
(Addr.)
F05.26
Terminal UP/DW controls
(0x0518)
frequency increase and
RUN
decrease rate
Note: When the terminal is active for a long time, the rate of increase or decrease will increase.
F05.27: Terminal emergency stop deceleration time
Code
Name
(Addr.)
F05.27
Terminal emergency stop
(0x0519)
deceleration time
RUN
Note: This parameter is valid only when [7: Emergency stop] is selected for the multi-function input terminal function.
F05.3x group: Pulse frequency input (PUL) terminal
F05.30: Pulse frequency input signal selection
Code
Name
(Addr.)
F05.30
Pulse frequency input
(0x051E)
signal selection
STOP
0: reserved
1: reserved
2: X4 terminal is selected as frequency input port, the maximum frequency is 100.00KHz
In the case of mode 2, F05.31, F05.33, and C00.19 are 2 decimal places.
Note:
The pulse frequency signal recommends a duty cycle of 50%.
F05.31~F05.34: PUL input linear processing
Code
Name
(Addr.)
F05.31
PUL
input
(0x051F)
frequency
RUN
F05.32
PUL
input
(0x0520)
frequency corresponding
RUN
setting
F05.33
PUL
input
(0x0521)
frequency
RUN
F05.34
PUL
input
(0x0522)
frequency corresponding
RUN
setting
The linear processing of the PUL input frequency is shown below:
Content
V/F SVC
Set terminal UP/DW to control the frequency increase and decrease rate
Content
V/F SVC
Set the deceleration time under the terminal emergency stop command
Content
V/F SVC
Select the matching mode according to the signal input on the terminal port
Content
V/F SVC
minimum
Set the lowest frequency that can be accepted, the frequency signal below
this value, and process according to the frequency
minimum
V/F SVC
Set the percentage of the set value corresponding to the PUL minimum input
frequency
V/F SVC
maximum
Set the maximum frequency that can be accepted, the frequency signal
higher than this value, and process according to the frequency
maximum
V/F SVC
Set the percentage of the set value corresponding to the maximum input
frequency of PUL
133
Parameter details
Factory setting
(Setting range)
0.50
(0.01 ~ 50.00Hz/s)
Factory setting
(Setting range)
1.00s
(0.01 ~ 650.00s)
Factory setting
(Setting range)
2
(0 ~ 2)
Factory setting
(Setting range)
0.000KHz
(0 ~ 50.000KHz,
F05.30=0)
(0 ~ 100.00KHz,
F05.30=1、2)
0.00%
(0.00 ~ 100.00%)
5.000KHz
(0 ~ 50.000KHz,
F05.30=0)
(0 ~ 100.00KHz,
F05.30=1、2)
100.00%
(0.00 ~ 100.00%)