terminal is invalid, and select PID parameter group 2 when the terminal is valid.
2: Switch according to deviation
selects parameter group 1; when the absolute value of deviation between PID given and feedback is greater than [F13.19 When the PID parameter selects
parameter group 2; when the absolute value of the deviation between the PID reference and the feedback is between the switching deviation low value
[F13.18] and the switching deviation high value [F13.19], the PID parameter is two The linear interpolation value of the group PID parameters is shown in
the figure below.
0
Switching the PID parameters according to the deviation
Code (Addr.)
Name
F13.18
Switching
(0x0D12)
low value
RUN
Code (Addr.)
Name
F13.19
Switching
(0x0D13)
high value
RUN
fferential Limiting
Code (Addr.)
Name
F13.21
(0x0D15)
Differential limiting
RUN
Differential limiting is used to set the range of the PID differential output. In the PID regulator, the effect of the differential is sensitive, and it is easy to cause
the system to oscillate. Generally, the effect of PID differentiation is limited to a small range.
Code (Addr.)
Name
F13.22
(0x0D16)
PID output upper limit
RUN
Code (Addr.)
Name
F13.23
(0x0D17)
PID output lower limit
RUN
Code (Addr.)
Name
When the absolute value of deviation between PID reference and feedback is less than [F13.18], PID parameter
Proportional gain (P)
Integration time (I)
Differential gain (D)
Switching deviation low value
Content
deviation
V/F SVC
Content
deviation
V/F SVC
Content
V/F SVC
Content
V/F SVC
Used to set the PID output upper limit value
Content
V/F SVC
Used to set the PID output lower limit value
Content
Proportional gain 2
Integration time 2
Differential gain 2
Proportional gain 1
Integration time 1
Differential gain 1
Switching deviation high value
179
Parameter details
PID deviation
Factory setting
(Setting range)
20.0%
(0.0~100.0%)
Factory setting
(Setting range)
80.0%
(0.0~100.0%)
Factory setting
(Setting range)
5.0%
(0.0~100.0%)
Factory setting
(Setting range)
100.0%
(0.0~100.0%)
Factory setting
(Setting range)
0.0%
(-100.0~Fb.19)
Factory setting
(Setting range)
AC10 Series Frequency Inverter Technical Manual