Download Print this page

Veichi AC10 Series Technical Manual page 148

Advertisement

Parameter details
F06.40: Frequency detection value 1
Code (Addr.)
Name
F06.40
Frequency detection value
(0x0628)
1
RUN
Note:
The comparison object of the frequency detection value is the target frequency.
Code (Addr.)
Name
F06.41
Frequency
(0x0629)
amplitude 1
RUN
Code (Addr.)
Name
F06.42
Frequency detection value
(0x062A)
2
RUN
Note:
The comparison object of the frequency detection value is the target frequency.
Code (Addr.)
Name
F06.43
Frequency detection range
(0x062B)
2
RUN
Code (Addr.)
Name
F06.44
The
given
(0x062C)
reaches
the
RUN
range
The frequency arrival output is shown below:
Note:
The comparison object of the frequency detection value is the target frequency.
F06.5x group: Monitor parameter comparator output
The set of parameters sets any one of the monitoring parameters for comparison by the comparator, and selects a multi-function output terminal, an alarm
or an alarm according to the judgment result. Meet the comparison output of various monitoring variables.
F06.54: Comparator 1 (CP1)
Code (Addr.)
Name
AC10 Series Frequency Inverter Technical Manual
Content
V/F SVC
Set the frequency detection value
Content
detection
V/F SVC
Set the frequency detection range
Content
V/F SVC
Set the frequency detection value
Content
V/F SVC
Set the frequency detection range
Content
frequency
V/F SVC
detection
Set the given frequency to reach the detection range
Frequency arrival detection diagram
Content
144
Factory setting
(Setting range)
30.00Hz
(0.00 ~ F01.10)
Factory setting
(Setting range)
1.00Hz
(0.00 ~ F01.10)
Factory setting
(Setting range)
50.00Hz
(0.00 ~ F01.10)
Factory setting
(Setting range)
1.00Hz
(0.00 ~ F01.10)
Factory setting
(Setting range)
2.00Hz
(0.00 ~ F01.10)
Factory setting
(Setting range)

Advertisement