Veichi AC10 Series Technical Manual page 134

Advertisement

Parameter details
Value].
44: DC braking command
When the drive is stopped, the DC braking function of the drive can be started. For the current during DC braking, refer to parameter F07.23 [DC Brake
Current] setting value. If a run or jog command is input, the DC brake will be released.
DC brake
command
Run
command
DC braking
state
Output
frequency
DC braking command diagram
45: Pre-excitation command terminal
This function is only valid during asynchronous machine vector control. When the drive is stopped, the pre-excitation function of the drive can be started.
If a run or jog command is input, the pre-excitation will be released.
46-47: Reserved
48: Command channel switches to keyboard
49: Command channel is switched to the terminal
50: Command channel switches to communication
51: Command channel switch to expansion card
The command channel switching terminal can be switched to four kinds of command settings, and the effective priority of the terminal is from keyboard to
terminal, communication, and expansion card from high to low.
Note: When both command channel terminals are valid at the same time, the command channel is selected as the keyboard by default.
52: Run prohibition
53: Forward transfer prohibition
54: Reverse prohibition
When the operation prohibition terminal selection is valid, the running command in the stop state is invalid, and the running state is free to stop;
When the forward rotation prohibition terminal selection is valid, the forward rotation running command is invalid in the stop state, and the free running is
stopped in the forward running state;
When the reverse prohibition terminal selection is valid, the reverse running command is invalid in the stop state, and the free running is stopped in the
reverse running state;
55-59: Reserved
60: Speed torque control switching
This function is valid under vector control. When the terminal is valid, the motor is switched from speed control to torque control.
61: Reserved
62-63: Reserved
F05.1x group: X1-X5 detection delay
F05.10~F05.11: Terminal X1 detection delay
Code (Addr.)
Name
F05.10
X1 effective detection
(0x050A)
delay
RUN
F05.11
X1 uneffective check
(0x050B)
delay
RUN
Note:
Increase the detection delay of terminal X1, and enhance the filtering effect on the input terminal signal.
Code (Addr.)
Name
F05.12
X2 effective detection
(0x050C)
delay
RUN
F05.13
X2 uneffective check
(0x050D)
delay
RUN
Note:
AC10 Series Frequency Inverter Technical Manual
ON
ON
Stop DC braking start
frequency
Content
V/F SVC
Delay time corresponding to the transition of the terminal X1 from the
inactive state to the active state
V/F SVC
Delay time corresponding to the transition of the terminal X1 from the active
state to the inactive state
Content
V/F SVC
Delay time corresponding to the transition of the terminal X1 from the
inactive state to the active state
V/F SVC
Delay time corresponding to the transition of the terminal X1 from the active
state to the inactive state
130
ON
ON
OFF
OFF
OFF
Factory setting
(Setting range)
0.010s
(0.000 ~ 6.000s)
0.010s
(0.000 ~ 6.000s)
Factory setting
(Setting range)
0.010s
(0.000 ~ 6.000s)
0.010s
(0.000 ~ 6.000s)