Veichi AC10 Series Technical Manual page 179

Advertisement

Code (Addr.)
Name
F12.11
Frequency
(0x0C0B)
custom
RUN
setting
Note:
The default is 0: it means invalid, other values indicate that the address has priority over the function code parameter address.
F12.12: Command given custom address setting
Code (Addr.)
Name
F12.12
Command
(0x0C0C)
custom
RUN
settings
Note:
Code (Addr.)
Name
F12.13
Command given as
(0x0C0D)
forward run command
RUN
value
Code (Addr.)
Name
F12.14
Command given as
(0x0C0E)
reverse run command
RUN
value
Code (Addr.)
Name
F12.15
Command given as
(0x0C0F)
stop command value
RUN
Code (Addr.)
Name
F12.16
Command given as
(0x0C10)
reset command value
RUN
11.15 F13 Group: Process PID Control
F13.00-F13.06: PID given and feedback
F13.00-F13.06: PID given and feedback
Code (Addr.)
Name
F13.00
PID controller given
(0x0D00)
signal source
RUN
Set the input channel of the PID controller given signal.
0: Keyboard digital PID reference
1: reserved
2: Voltage/current analog AI reference
3: Reserved
4: Reserved
5: Terminal pulse PUL reference
6: RS485 communication reference
7: Reserved
8: Terminal selection
The PID reference value is selected by the combination of multi-function input terminals. The multi-function input terminal is
set by [F05.00~F05.09].
9: Communication gives a working current.
Terminal switching selection diagram:
Content
given
V/F SVC
address
Used to set the frequency given custom address
Content
given
V/F SVC
address
Used to set the command given custom address
Content
V/F SVC
Used to set the forward run command custom value
Content
V/F SVC
Used to set the reverse run command custom value
Content
V/F SVC
Used to set the stop run command custom value
Content
V/F SVC
Used to set the fault reset command custom value
Content
V/F SVC
Used to set the PID signal to a given source
The PID reference value is determined by the setting value of [F13.01].
The PID reference is given by the voltage/current analog AI1.
PID reference is given by terminal pulse PUL.
PID reference value is given by RS485 communication.
175
Parameter details
Factory setting
(Setting range)
0x0000
(0000~FFFF)
Factory setting
(Setting range)
0x0000
(0000~FFFF)
Factory setting
(Setting range)
0x0001
(0000~FFFF)
Factory setting
(Setting range)
0x0002
(0000~FFFF)
Factory setting
(Setting range)
0x0005
(0000~FFFF)
Factory setting
(Setting range)
0x0007
(0000~FFFF)
Factory setting
(Setting range)
0
(0~9)
AC10 Series Frequency Inverter Technical Manual