Parameter details
F05.81
AI as a digital input
(0x0551)
terminal
STOP
selection
Note:
The AI function as a digital input terminal has the same function selection range as the terminals X1~X4.
Code
Name
(Addr.)
F05.82
(0x0552)
AI high level setting
RUN
F05.83
(0x0553)
AI low level setting
RUN
Note:
F05.82 setting value must be greater than F05.83 to effectively distinguish between high and low levels.
The AI input value is between F05.82 and F083, and the hysteresis is judged according to the previous state to distinguish between high and low
levels.
11.8 F06 Group: output terminal
The F06 parameter group is used to set the analog monitoring of the drive, and can select the selection of the monitoring item, the adjustment of the gain
and offset, and the selection of the output signal level.
F06.0x group: AO (analog, frequency) output
F06.0x is used to set the analog monitoring of the drive, and can select the selection of the monitoring item, the adjustment of the gain and offset, and the
selection of the output signal level.
The drive contains one AO output, and two different types of signal outputs, voltage and current, can be selected through the dial switch.
The calibration of the meter connected to the multi-function analog output terminal can be performed using F06.02, F06.03, F06.04, F06.05, and F06.06.
Parameter
Name
F06.00
AO output mode selection
F06.01
AO output selection
F06.02
AO output gain
F06.03
AO analog output offset
F06.04
AO output filtering
The benefits of gain and offset are shown in the figure below.
AO output analog (voltage /
AO output
gain 200%
Min
AC10 Series Frequency Inverter Technical Manual
V/F SVC
function
Set AI as a digital input terminal function
Content
V/F SVC
AI input sampling value is greater than the set value, is high
V/F SVC
The AI input sampling value is less than the set value and is low.
current)
AO output gain 100%
Monitoring
Max
AO analog output and gain, offset schematic
Predetermined area
0: 0~10V
1: 4.00~20.00mA
2: 0.00~20.00mA
0~19
25.0~200.0%
-10.0~10.0%
0.000~6.000s
AO output analog
(voltage / current)
AO offset
+10.0%
amount
Min
AO offset -10.0%
138
0
(0 ~ 95)
Factory setting
(Setting range)
70.00%
(0 ~ 100.00%)
30.00%
(0 ~ 100.00%)
Factory setting
0
0
100.0%
0.0%
0.010s
Monitoring
AO offset
amount
0.0%
Max