Download Print this page

Veichi AC10 Series Technical Manual page 116

Advertisement

Parameter details
Code
Name
(Addr.)
F01.32
Deceleration
(0x0121)
curve time
STOP
eceleration end S curve time
Code
Name
(Addr.)
F01.34
Deceleration end S curve
(0x0122)
time
STOP
Acceleration/deceleration time switching frequency
Code
Name
(Addr.)
F01.35
Acceleration/deceleratio
(0x0123)
n
time
RUN
frequency
When the output frequency reaches the set value of F01.35 [switching frequency of acceleration/deceleration time], the acceleration/deceleration time of
the drive will automatically switch, and the acceleration/deceleration time 1 will be switched to the acceleration/deceleration time 2.
Note:
When F01.35 = 0.00 Hz, the acceleration/deceleration time is invalid with the frequency switching function.
F01.4x group: PWM control
Code
Name
(Addr.)
F01.40
(0x0128)
Carrier frequency
RUN
When adjusting the electromagnetic noise or reducing the noise and leakage current, please change the setting.
Note:
The carrier defaults to 2.0 kHz during DC braking.
The carrier defaults to 2.0 kHz during self-learning.
F01.41: PWM control mode
Code
Name
(Addr.)
F01.41
(0x0129)
PWM control mode
RUN
Units: Carrier and temperature are associated
0: independent of temperature
1: related to temperature
When the drive temperature is too high, the drive will automatically reduce the carrier frequency; use this function to reduce the switching loss of the power
device and prevent the drive from skipping the thermal fault.
Tens: carrier is associated with output frequency
0: Independent of the output frequency
1: related to the output frequency
When the carrier and output frequency are valid, the drive can automatically adjust the carrier frequency according to the output frequency. This function
can improve the low frequency performance of the drive and the mute effect of high frequency.
Hundreds: Random PWM Enable
0: Forbidden
1: Enable
Thousands: PWM modulation
0: Only three-phase modulation is used
1: Two-phase three-phase modulation automatically switches
11.4 F02 Group: motor 1 parameters
The F02 group parameters are used to set the motor 1 parameters and motor application parameters.
F02.0x group: basic motor parameters and self-learning options
AC10 Series Frequency Inverter Technical Manual
Content
start
S
V/F SVC
Set the deceleration start S curve time
Content
V/F SVC
Set the deceleration end S curve time
Content
V/F SVC
switching
Acceleration/deceleration time switching frequency
Content
V/F SVC
Set the switching frequency (carrier frequency) of the power transistor in the
drive.
Content
V/F SVC
Optimize PWM control with this parameter setting
Select the PWM mode of the drive
112
Factory setting
(Setting range)
0.20
(0.01 ~ 10.00s)
Factory setting
(Setting range)
0.20
(0.01 ~ 10.00s)
Factory setting
(Setting range)
0.00Hz
(0.00 ~ F01.10)
Factory setting
(Setting range)
4.0kHz
(1.0 ~ 16.0kHz)
Factory setting
(Setting range)
0x1111
(0x0000 ~ 0x1111)

Advertisement