Note: The upper and lower limits are limited after adding the absolute value to the linear processing of the torque reference command.
Speed Limit
F03.54: Torque control forward speed limit selection
Code (Addr.)
Name
F03.54
Torque control forward
(0x0336)
speed limit selection
RUN
0: Forward speed limit digital setting F03.56
1: integrated keyboard potentiometer given × F03.56
2: AI × F03.56
3: Reserved
4: Reserved
5: PUL× F03.56
6: RS485 communication given (communication address is 0x3006) × F03.56
7: Reserved
Code (Addr.)
Name
F03.55
Torque control reverse
(0x0337)
speed limit selection
RUN
0: Reverse speed limit digital setting F03.57
1: integrated keyboard potentiometer given × F03.57
2: AI × F03.57
3: Reserved
4: Reserved
5: PUL × F03.57
6: RS485 communication given (communication address is 0x3007) × F03.57
7: Reserved
Code (Addr.)
Name
F03.56
Forward speed limit
(0x0338)
digital setting / gain
RUN
Note:
When set as the forward speed limit digital setting, the set value 100.0% corresponds to the maximum frequency.
Code (Addr.)
Name
F03.57
Reverse speed limit
(0x0339)
digital setting / gain
RUN
Note:
When the reverse speed limit digital setting is set, the set value 100.0% corresponds to the maximum frequency.
Torque reference command gain switching
When the output frequency is lower than F03.58, you could increase or decrease the given torque by setting F03.59.
F03.58: given torque gain switching frequency
Code (Addr.)
Name
F03.58
Given
torque
(0x033A)
switching frequency
RUN
Code (Addr.)
Name
F03.59
(0x033B)
Given torque gain
RUN
Content
SVC
Set torque control forward speed limit selection
Content
SVC
Set torque control reverse speed limit selection
Content
SVC
Set forward speed limit digital setting / gain
Content
SVC
Set reverse speed limit digital setting / gain
Content
gain
SVC
Set the given torque gain switching frequency
Content
SVC
Set the given torque gain
121
Parameter details
Factory setting
(Setting range)
0
(0 ~ 7)
Factory setting
(Setting range)
0
(0 ~ 7)
Factory setting
(Setting range)
100.0%
(0.0 ~ 100.0%)
Factory setting
(Setting range)
100.0%
(0.0 ~ 100.0%)
Factory setting
(Setting range)
2.00Hz
(0.00 ~ 50.00Hz)
Factory setting
(Setting range)
100.0%
(0.0 ~ 500.0%)
AC10 Series Frequency Inverter Technical Manual