Download Print this page

Veichi AC10 Series Technical Manual page 83

Advertisement

F07.11
(0x070B)
Shutdown detection frequency
RUN
F07.12
(0x070C)
Stop and restart limit time
STOP
F07.15
Insufficient lower limit frequency action
(0x070F)
selection
RUN
F07.16
(0x0710)
Zero speed torque retention factor
RUN
F07.17
(0x0711)
Zero speed torque holding time
RUN
F07.18
(0x0712)
Positive reversal dead time
STOP
F07.2x group: DC braking and speed tracking
Parameter
(address)
Name
djustable
attribute
F07.20
(0x0714)
Braking current before starting
STOP
F07.21
Braking time before starting
(0x0715)
STOP
F07.22
(0x0716)
DC braking start frequency
STOP
F07.23
(0x0717)
DC braking current
STOP
F07.24
(0x0718)
DC braking time during shutdown
STOP
F07.25
(0x0719)
Speed tracking mode
STOP
F07.26
(0x071A)
Speed tracking speed
STOP
F07.27
Speed tracking stop delay
(0x071B)
STOP
F07.28
(0x071C)
Speed tracking current
STOP
F07.3x group: Jog
Parameter
(address)
Name
djustable
attribute
V/F SVC
When decelerating to stop, when the drive output frequency is
less than this value, it will enter the stop state.
V/F SVC
Waiting time after restarting after shutdown
V/F SVC
0 : Run according to frequency command
1 : Free running stops, enters the pause state
2 : The following limited frequency operation
3 : Zero speed operation
V/F SVC
V/F SVC
V/F SVC
Positive and negative switching, zero frequency maintenance
time
Content
V/F SVC
V/F SVC
V/F SVC
V/F SVC
The reference is the rated current of the drive, and the internal
limit does not exceed the rated current of the motor.
V/F SVC
V/F SVC
LED "0" digit: Search method
0: Search from the maximum frequency
1: Search from stop frequency
LED "00" digit: Reverse search
0: Off
1: Open
LED "000" digit: Search Source
0: Software search
1: Hardware search
LED "0000" digit: Reserved
V/F SVC
V/F SVC
V/F SVC
Content
79
0.50Hz
(0.00~Upper
limit
digital setting)
0.00s
(0.00~60.00s)
0
(0~3)
60.0%
(0.0~150.0%)
0s
(0.0~6000.0s)
0.0s
(0.0~120.0s)
Factory default
(setting range)
60.0%
(0.0~150.0%)
0.0s
(0.0~60.0s)
1.00Hz
(0.00~50.00Hz)
60.0%
(0.0~150.0%)
0.0s
(0.0~60.0s)
0000
(0000~0111)
0.5s
(0.0~60.0s)
1.00s
(0.0~60.0s)
120.0%
(0.0~400.0%)
Factory default
(setting range)
AC10 Series Frequency Inverter Technical Manual
Function Table
frequency

Advertisement

loading

This manual is also suitable for:

Sis series