About Cip Safety In Devicenet Safety Architectures - Rockwell Automation 1732DS-IB8 User Manual

Guard i/o devicenet safety modules
Hide thumbs Also See for 1732DS-IB8:
Table of Contents

Advertisement

14
About the Modules
About CIP Safety in
DeviceNet Safety
Architectures
SmartGuard 600
Controller
CompactBlock
Guard I/O
Module
Safety Communication
Standard Communication
Publication 1791DS-UM001H-EN-P - April 2009
Use Guard I/O modules in DeviceNet safety architectures as shown in
the figure.
The Guard I/O family is a set of I/O modules that when connected to
a DeviceNet safety network are suitable for applications up to SIL3, as
defined in the IEC 61508 standard, and Safety Category 4, as defined
in the EN 954-1 standard.
Guard I/O Modules in DeviceNet Safety Architectures
Logix Controller GuardLogix Controller
RSNetWorx,
RSLogix 5000, and
RSLogixGuard Plus
Software
Safety input devices such as emergency-stop switches and safety
output devices, such as safety contactors, can be connected to safety
I/O blocks. Standard devices, such as proximity switches,
pushbuttons, or lamps, can also be connected to safety I/O blocks.
Safety PLC controllers or safety network controllers control the safety
outputs. Safety PLC controllers, safety network controllers, or standard
PLC controllers can control the standard outputs.
The modules provide self-diagnostics to test the electronics within the
module. The safety outputs provide a pulse test feature for diagnosing
the external wiring of field actuators. Testing of input wiring is by
connecting the field input devices to one of the pulse test outputs
provided by the modules. Any pulse test outputs not used to test input
wiring can be used as a standard output. At least one of these
standard outputs is configurable with current monitoring to use it for
control and monitoring of a muting lamp.
Guard PLC Controller
ArmorBlock Guard I/O
Module
DeviceNet
Scanner
Interface
44196