60
Configure Modules in RSLogix 5000 Software

Save Module Configuration

Status Data Supported by
Each Module
Publication 1791DS-UM001H-EN-P - April 2009
We recommend that after a module is configured you save your work.
After downloading the program, if the MS and NS LED indicators on
the 1791DS module are not both solid green, this may be due to loss
of ownership. The ownership is based on the following:
1791DS DeviceNet node number
1791DS safety network number
GuardLogix slot number
GuardLogix safety network number
If any of these change, the connection between the GuardLogix
module and the 1791DS module is lost, and the yellow yield in the
RSLogix 5000 tree appears. Reset ownership to reestablish the
connection using this procedure.
1. From within RSLogix 5000 software, open the safety I/O module
properties.
2. Click the Safety tab.
3. From the dialog, click Reset ownership.
See Appendix D, Configuration Reference Information, for the tables
that show the I/O data supported by each module. Refer to I/O
Assembly Data for data arrangements.
For I/O data, safety connections for up to four items, including one
output, can be allocated for the master unit, and standard connections
for up to two items can be allocated for the master unit (scanner).