Follow this procedure to complete entries from the Output
Configuration dialog.
1. For Point Operation, select Single or Dual, noting the following
if you click Dual:
The 1791DS module always sets the high or low as a pair.
You must always match the two ouputs as a pair in software
as well.
2. For Point Mode, select Not Used, Safety, or Safety Pulse Test,
referring to the Safety Input Parameters table for additional
information.
3. Select a value for Output Error Latch Time.
4. Click Apply from the bottom of the dialog.
Configure Modules in RSLogix 5000 Software
Publication 1791DS-UM001H-EN-P - April 2009
59