Rockwell Automation 1732DS-IB8 User Manual page 116

Guard i/o devicenet safety modules
Hide thumbs Also See for 1732DS-IB8:
Table of Contents

Advertisement

112
DeviceNet Explicit Messages
Monitoring the Test Output Point
Explicit
Read/
Function
Message
Write
Safety Output
Read
Reads the cause
Cause of Error
for
(Fault)
the normal flag
Information
(1...8) specified
by the Instance
ID turning OFF.
Setting Hold/Clear for Communication Errors (Test Output)
Explicit Message Read/
Write
Setting for Output
Read
Status (Hold or
Clear) after
Communication
Error
Setting for Output
Write
Status (Hold or
Clear) after
Communication
Error
Publication 1791DS-UM001H-EN-P - April 2009
Command (hex)
Service
Class
Code
ID
0E
09
Function
Command (hex)
Service
Code
Reads whether hold
0E
or clear is set as the
output status after a
communication error for
an output specified by
the instance ID. The
setting can be read
for a specified number
of points.
Sets whether hold or
10
clear as the output
status after a
communication error
for an output
specified by the
instance ID. The
setting can be read
for a specified
number of points.
Instance
Attribute
Data Size
ID
ID
01...04
6E
-
Class
Instance
Attribute
ID
ID
ID
09
01...08
05
09
01...08
05
Response (hex)
0 = No error
01 :
Configuration invalid
02 :
Overload detected
03 :
Cross circuit detected
05 :
Output ON error
06 :
Undercurrent detected for
muting lamp
Response
(hex)
Data Size
-
1 byte
00 : Clear
01 : Hold
1 byte
00 : Clear
01 : Hold

Advertisement