Rockwell Automation 1732DS-IB8 User Manual page 114

Guard i/o devicenet safety modules
Hide thumbs Also See for 1732DS-IB8:
Table of Contents

Advertisement

110
DeviceNet Explicit Messages
Error Codes
Response
Error Name
Code
(hex)
08FF
Service not supported
09FF
Invalid attribute value
16FF
Object does not exist
15FF
Too much data
13FF
Not enough data
0CFF
Object state conflict
20FF
Invalid parameter
0EFF
Attribute is not setable
10FF
Device state conflict
14FF
Attribute not supported
19FF
Store operation failure
2AFF
Group 2 only server general failure The specified command or attribute is not supported or the attribute was not set.
Publication 1791DS-UM001H-EN-P - April 2009
• Service Code - For normal completions, the service code
specified in the command with the leftmost bit turned ON is
stored as shown in the following table.
Function, Command Service Code, and Response Service Code
Function
Command Service Code (hex) Response Service Code (hex)
Read Data
10
Write Data
0E
Reset
05
Save
16
When an error response is returned for an explicit message, the value
is always 94 hex.
• Data - Read data is included only when a read command is
executed.
• Error code - The explicit message error code. For details, refer to
the list of error codes in the following table.
Cause
The service code is incorrect.
The specified attribute value is not supported. The data written was outside valid range.
The specified instance ID is not supported.
The data is larger than the specified size.
The data is smaller than the specified size.
The specified command cannot be executed due to an internal error.
The specified operation command data is not supported.
An attribute ID supported only for reading has been executed for a write service code.
The specified command cannot be executed due to an internal error.
The specified attribute is not supported.
The data cannot be stored in memory.
90
8E
85
96