178
Specifications
Publication 1791DS-UM001H-EN-P - April 2009
Attribute
Aggregate Current of
Outputs per Module
Pilot Duty Rating
Number of Outputs
(1)
Includes the presence of a single P stuck-high or M stuck-low short.
General
Attribute
North American Temp Code T4A
Enclosure Type Rating
Communication Power
Supply Voltage
Communication Current
Consumption
Operating Voltage Range
Isolation Voltage
Product Temperature
Versus Current Derating
(1)
Wiring Category
Wire Size
Weight, Approx.
Dimensions (HxWxD),
Approx.
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1.
Value
8 A @ 40 °C
6 A @ 60 °C
2.5 A inrush
4 dual channel
Value
Meets IP20
11...25V dc (supplied from communication power supply)
85 mA at 24V dc
19.2...28.8V dc (24V dc, -20...+20%)
50V (continuous), Basic Insulation
Tested at 800V dc for 60 s, between Input and Output
Channels, and between Network and I/O channels
8 A
7 A
6 A
-20 °C
Product Temperature Versus Current Derating
(combined current from both input and output supplies)
2 - on signal ports
2 - on power ports
2 -on communication ports
2
0.34...2.5 mm
(24...16 AWG) solid or stranded
copper wire rated at 75 °C (167 °F ) or greater 1.2 mm
(3/64 in.) insulation max
600 g (1.32 lb)
81 x 170 x 76 mm (3.1 x 6.7 x 2.9 in.) with terminal block
66 x 170 x 60 mm (2.6 x 6.7 x 2.4 in.) without terminal block
40 °C 50 °C 60 °C
44199