Work with Test Output
Configuration Dialog
Test Output Parameters
(1)
Value
Parameter Name
x
Test Output
Not Used
Mode
Standard
Pulse Test
Power Supply
Muting Lamp Output
(Terminal T3/T7 only)
(2)
Clear OFF
Test Output
Fault Action
Hold last state
(1)
Parameters directly related to safety are marked with an X in the left column.
(2)
Can only be read/write via explicit messaging.
Read this for information about how to work with the Test Output
Configuration dialog, referring to the table that provides information
on configuring test outputs.
Description
The standard output is disabled.
The output point is enabled for use by the GuardLogix controller.
The test output is being used as a pulse test source.
A constant 24V is placed on the output terminal. It can be used to provide
power to a field device.
An indicator lamp is connected to the output. When this lamp is energized, a
burned-out bulb, broken wire, or short to GND error condition can be
detected. Typically, the lamp is an indicator used in light curtain applications.
If communication to the module times out, test outputs can either go to the
OFF state or hold last state.
Complete entries on the Test Output dialog, referring to the figure.
Configure Modules in RSLogix 5000 Software
Publication 1791DS-UM001H-EN-P - April 2009
57
Default
Not Used
Clear OFF