Module Status Indicator
State
Status
Off
No Power or Autobauding
Solid Green Normal Operation
Solid Red
Unrecoverable Fault
Flashing
Module Needs Commissioning
Green
Due to Missing, Incomplete, or
Incorrect Configuration
Flashing Red Recoverable Fault or
User-initiated Firmware Update
Flashing Red
Device in Self Test
and Green
Network Status Indicator
State
Status
Off
Module Not Online or No Power
Flashing
Module Online With No
Green
Connections in Established State
Solid Green Module Online with Connections
in Established State
Flashing
One or more I/O Connections in
Red
Timed-out State or User-initiated
Firmware Update
Solid Red
Critical Link Failure
Flashing
Communication Faulted Module
Red and
Green
Configuration Lock Indicator
Indicator State
Off
No configuration or the configuration is
owned by a CIP safety originator, such as
GuardLogix
Solid
Locked
Yellow
Flashing
Not locked
Yellow
Description
No power is applied to the DeviceNet connector.
The module is operating normally.
The module has detected an unrecoverable fault.
Module is unconfigured.
The module has detected a recoverable fault or
user-initiated firmware update is in progress.
The module is performing its power-cycle
diagnostic tests.
Description
The module is not online with the network.
The module identified the communication rate of the
network but no connections are established.
The module is operating normally.
The module detected a recoverable network fault, or
user-initiated firmware update is in progress.
The module detected an error that prevents it from
communicating on the network.
The module detected a network access error and is in
communication faulted state. The module has received
and accepted an Identity Communication Faulted
Request-long protocol message.
Description
Invalid configuration data.
Valid configuration, locked by a network configuration
tool such as RSNetWorx for DeviceNet software.
Valid configuration, owned by a software configuration
tool such as RSNetWorx for DeviceNet software.
Interpret the LED Indicators
Recommended Action
Apply power to this connector.
None.
Cycle power to the module. If problem
persists, replace the module.
Reconfigure the module. For additional
information, inspect Network Status
indicator.
Cycle power to the module or reset the
module.
Wait for the module to complete its
power-cycle diagnostics.
Recommended Action
Verify your network.
Verify your network and module
configuration.
None.
Verify your network and module
configuration.
Cycle power to the module, If
problem persists, replace the
module.
Verify your network and module
configuration.
Recommended Action
None.
None.
None.
Publication 1791DS-UM001H-EN-P - April 2009