Environmental Specifications
Attribute
Temperature, operating
Temperature, storage
Relative Humidity
Vibration
Shock, Operating
Shock, Nonoperating
Emissions
ESD Immunity
Radiated RF Immunity
Conducted RF Immunity
EFT/B Immunity
Surge Transient Immunity
Value
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...60 °C (-4...140 °F)
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock):
-40...85 °C (-40...185 °F)
IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp
Heat):
5...95% noncondensing
IEC 60068-2-6 (Test Fc, Operating):
5 g at 10...500 Hz
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50 g
CISPR 11: Group 1, Class A
IEC 61000-4-2:
8 kV contact discharges
15 kV air discharges
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80%AM from
80 MHz...2000 MHz
10V/m with 200 Hz 50% Pulse 100%AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz
1V/m with 1 kHz sine-wave 80%AM from 2000...2700 MHz
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from
150 kHz...80 MHz
IEC 61000-4-4:
±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on signal ports
±2 kV at 5 kHz on communication\ ports
IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM)
on power ports
±1 kV line-line (DM) and ±2 kV line-earth (CM)
on signal ports
±2 kV line-earth (CM) on communication ports