The example shows wiring and configuration when using a 1791DS-IB8XOBV4 module with solid state outputs in Dual-channel mode.
Note that all safety outputs of a 1791DS-IB8XOBV4 module are permanently configured for use as Dual-channel mode only.
When used in combination with the programs of the safety controller, this circuit configuration is Safety Category 4 in accordance with EN954-1
requirements.
Publication 1791DS-UM001H-EN-P - April 2009
1791DS-IB8XOBV4 Dual-load Bipolar Outputs - Example 2
IMPORTANT
FE
O0
Out
-
P
18
19
In order for the bipolar safety outputs to work correctly, you
must connect the devices that are being controlled as shown in
this figure. Connection of devices directly to 24V DC, 0V DC, or
Ground is strictly prohibited.