Interpret the LED Indicators
Safety Input Status Indicator
State
Status
Off
Safety Input Off Or Module
Being Configured
Solid Yellow Safety Input On
Solid Red
Fault Detected
Flashing Red Partner Fault Detected
Test Output Status Indicator (1791DS-IB8XOBV4 only
State
Status
Off
Test Output Off Or Module
Being Configured
Solid Yellow Output On
Solid Red
Fault Detected
Safety Output Status Indicator
State
Status
Off
Safety Output Off Or
Module Being Configured
Solid Yellow Safety Output On
Solid Red
Fault Detected
Flashing Red Partner Fault Detected
Publication 1791DS-UM001H-EN-P - April 2009
Description
The safety input is off or the module is being
configured.
The safety input is on.
A fault in the external wiring or input circuit
detected.
A fault in the partner input circuit of a dual input
configuration detected.
Description
The test output is off or the module is being
configured.
Output is on.
A fault in the external wiring or input circuit
detected.
Description
The safety output is off or the module is being
configured.
The safety output is on.
A fault in the output circuit was detected.
Both tags in a dual channel circuit do not have the
same value.
A fault in the partner output circuit of a dual
output configuration was detected.
Recommended Action
Turn the safety input on or wait for the
module to be configured.
None.
Check configuration, field wiring, and
devices. If no problem found, replace
module.
Check the field wiring and verify your
configuration for the partner circuit. If no
problem found, replace module.
Recommended Action
Turn the test output on or wait for the
module to be configured.
None.
Check field wiring. If no problem found,
replace module. For outputs configured for
muting could indicate undercurrent or
burned-out lamp.
Recommended Action
Turn the safety output on or wait for the
module to be configured.
None.
Check the circuit wiring and end device. If
no problem found, replace module.
Make sure logic is driving tag values to the
same state (off or on).
Check the circuit wiring and end device of
the partner. If no problem found, replace
module.