Test Output Error
Code (hex)
Error Content
01
Configuration invalid
02
Overload detected
05
Output ON error
06
Undercurrent detected for
muting lamp
Explicit Message for Reading the Cause of the Test Output Error
Explicit
Read/
Function
Message
Write
Test Output
Read
Reads the cause
Cause of
for the normal (OK)
Error
flag (1...4)
Information
specified by the
Read
instance ID
(1)
The instance numbers for test outputs 0...7 are 1...8 (01...08 hex), respectively.
Safety Output Errors
Code (hex)
Error Content
01
Configuration invalid
02
Over current detected
03
Short-circuit detected
04
Output ON error
05
Error in the other dual channel
output
06
Internal-relay output circuit
error
07
Relay error
08
Output data error
09
Short-circuit detected in output Short-circuit between output signal lines.
Probable Cause
The configuration is invalid.
1) Ground fault or short-circuit of an output signal line.
2) Trouble with the connected device.
1) The power source (positive side) is in contact with the
output signal line.
2) Trouble with the internal circuits.
Trouble with the connected device.
Command
Service
Class
Instance
Code
ID
ID (hex)
(hex)
(hex)
OE
09
01...08
(1)
Probable Cause
The configuration is invalid.
Trouble with the connected device.
Ground fault of the output signal line.
1) The power source (positive side) is in
contact with the output signal line.
2) Trouble with the internal circuit.
Dual channels are set and an error occurred
in the other channel.
Trouble with the internal circuit
(1791DS-IB4XOW4 module only).
Trouble with the relay
(1791DS-IB4XOW4 module only).
Wrong setting for output data.
Recommended Action
Configure the module correctly.
1) Check the wiring.
2) Replace the connected device.
1) Check the wiring.
2) Replace the module.
Replace the connected device.
Response (hex)
Attribute
Data
ID (hex)
Size
76
-
0:No Error
01: Configuration invalid
02: Overload detected
05: Output ON error detected
06: Undercurrent detected for muting
lamp
Recommended Action
Configure the module correctly.
Replace the connected device.
Check the wiring.
1)Check the wiring.
2)Replace the module.
Remove the error in the other channel.
Replace the module.
Replace the relay.
Check the program.
Check the wiring.
Publication 1791DS-UM001H-EN-P - April 2009
Maintain Your Modules
105