46
Configure Modules in RSLogix 5000 Software
Publication 1791DS-UM001H-EN-P - April 2009
Input Data Options
Choose from these options:
Safety - Selecting Safety creates these tags for the target module:
– RunMode: Module mode
– ConnectionFaulted: Communications status
– Safety Data: Safety inputs from module
Safety-Readback - This selection is not available for input-only
safety modules. Selecting Safety-Readback creates both safety
and readback tags, with readback indicating the presence of 24V
on the output terminal.
Small Safety - This selection is for 12-point safety input modules
that use 8 or fewer safety inputs. The selection reduces the
amount of data the 12-point module sends to the controller to
improve network performance. Safety data and point status tags
are created. Point status is diagnostic status for each of the 8
input points.