Install and Connect Your Modules

Set the Node Address

Configure the Module

Publication 1791DS-UM001H-EN-P - April 2009
To set the node address, follow these procedures.
The node-address setting rotary switches must be set while
IMPORTANT
the communication power supply is turned off.
Sample Node Address Digits
0
2
8
8
4
6
6
|
X10
Tens Digit
Ones Digit
1. Set the node address using the two rotary switches on the front
panel of the module, noting that the default setting is 63 and a
value between 00...63 is valid for proper use.
2. Use the left rotary switch to set the tens digit of node address
(decimal).
3. Use the right rotary switch to set the ones digit.
If a node address from 64...99 is set, the node address can be set from
RSNetWorx for DeviceNet software.
Configure the module using RSNetWorx for DeviceNet or RSLogix
5000 software.
You can refer to this manual the corresponding-module configuration
software tool and its help files in RSLogix 5000 or RSNetWorx for
DeviceNet software.