When Main power is off, the System OK LED on the front panel begins blinking,
indicating that the server is in Standby power mode. See
Indicators" on page
Disconnect the power cords and data cables from the server.
2.
See
"Disconnect Cables From the Server" on page
When you power down the server using the On/Standby button, the server enters
Caution -
Standby power mode. Power is still directed to the service processor and power supply fans. To
completely power off the server, you must disconnect the power cords from the power supplies.
Related Information
"Power Down the Server for Immediate Shutdown Using the Oracle ILOM
■
CLI" on page 59
"Power Down the Server for Immediate Shutdown Using the Oracle ILOM Web
■
Interface" on page 60
"Power On the Server" on page 222
■
Disconnect Cables From the Server
The system supplies Standby power to the circuit boards even when the system is
Caution -
powered off.
Label all cables connected to the server.
1.
Power down the server.
2.
See
"Powering Down the Server" on page
3.
Disconnect the power cords from the rear of the server.
4.
Disconnect all data cables from the rear of the server.
If your rackmount kit includes a cable management device, remove the cables
5.
from it.
Depending on the components that you are servicing, either extend the server to
6.
the maintenance position, or remove the server from the rack.
31.
55.
Disconnect Cables From the Server
"Server System-Level Status
61.
Preparing for Service
61