13.8 IGNITION STATE

The controller transitions to the Ignition state to initiate pilot light off for all connected pilot cards. The Ignition state
is a fuel state that energizes the pilot valve outputs and ignition outputs but holds all main valve outputs de-
energized. Successful pilot ignition is required for the controller to transition into any other fuel state.
Proven Pre-Purge
13.8.1 SAFETY OUTPUT BEHAVIOR - IGNITION STATE
Card
PF3101-00 BMS Controller card
PF3102-00 Ion Pilot card
PF3102-01 UV Pilot card
13.8.2 TRANSITIONS TO THE IGNITION STATE
From
Scenario
Waiting
Any
Proven Pre-
Pre-purge sequence completed
Purge
successfully
13.8.3 TRANSITIONS FROM THE IGNITION STATE
To
Scenario
Any
Controller stopped by user
Pilot ignition failure
Lockout
Flame loss
Flame detected upon transition
into Ignition state
Any
Waiting
Pilot Ignition failure
Flame loss
Pilot
Successful pilot flame ignition
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Waiting
Condition
FARC Enable setting is Disabled, AND
No alarm or wait conditions present
No alarm or wait conditions present
Condition
Alarm condition present
Any
Pilot ignition has failed 3 consecutive times
Relight Attempts setting has been exceeded
Any
Wait condition present
Pilot ignition has failed less than 3 times consecutively
Relight Attempts settings has not been exceeded
No alarm or wait conditions present, AND
Minimum Pilots Running setting is satisfied
Ignition
Output
Pilot
SSV1
SSV2
Valve
Coil
Ignition Enable
PF3100 Product Manual
DOC-001149 v8.0
Lockout
Waiting
Pilot
Output State
Energized
De-energized
De-energized
Energized
Energized
Closed
97