ProFire PF3100 Product Manual page 155

Hide thumbs Also See for PF3100:
Table of Contents

Advertisement

16.10.3.2
IGNITION
Setting
Ignition Mode
Relight Attempts
Minimum Pilots Running
Pilot Relight Mode
Pilot Relight Timeout
Pilot Flame Fail (FFRT)
Main Flame Fail (FFRT)
16.10.3.3
VALVES
Setting
Pilot Valve PWM
SSV1 PWM
SSV2 PWM
High Fire PWM
HFV Output Mode
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Default
Options
Coil
3 attempts
1
Refer to
During Flame Fail
and descriptions.
30 s
4 s
4 s
Default
Options
60 %
20 % - 100 %
60 %
20 % - 100 %
60 %
20 % - 100 %
60 %
20 % - 100 %
Valve
Forced Draft
Valve
Fan
Purge Fan
Description
Pilot Wizard Ignition Settings Tab
Description
Specifies the duty cycle of the BMS Controller Pilot valve
output and the Ion Pilot card Valve output.
Specifies the duty cycle of the SSV1 valve output.
Specifies the duty cycle of the SSV2 valve output.
Specifies the duty cycle of the HFV valve output.
The HFV output is connected to a normally closed high
fire valve.
The HFV output is connected to a relay enabling a
forced draft fan.
The HFV output is connected to a relay enabling a purge
fan.
PF3100 Product Manual
DOC-001149 v8.0
section for configuration options
155