17.6 REIGNITING A LOST PILOT
Lost pilots can be re-ignited without stopping the controller for multi-pilot applications where one or more pilot
flames are lost and the Minimum Pilots Running setting is still satisfied. From the Controller Status Screen, select
the lost pilot and press
17.7 ACKNOWLEDGING LOCKOUTS
Lockout messages appear when a controller enters the Lockout state and must be acknowledged for the controller
to transition to any other state. The following methods can be used to acknowledge and clear a lockout message
from the screen:
•
User Interface: Press
External Ignition Switch: Toggle switch from Run to Stop to Run position within 30 seconds.
•
•
Remote Start input: Toggle input from energized to de-energized to energized within 30 seconds.
Modbus – Write Acknowledge command to the Clear Shutdown Code Modbus register (30143/40143). Refer
•
to
PF3107-00 Modbus Register Map
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
to attempt pilot reignition while maintaining the current controller state.
.
for details.
PF3100 Product Manual
DOC-001149 v8.0
166