11 PF3107-00 MODBUS CARD

The Modbus Comm card is a PFRN bus expansion and communication card designed to connect between a UI card
and one or more BMS controller cards to facilitate the following:
1. PFRN Controller Network expansion to allow additional BMS controller cards to be added to the system.
2. Modbus communication capabilities to each BMS controller card in the system.
4
Signal
In
5
PWR
Out
6
7

11.1 TERMINAL RATINGS

Name
Power In
Start Input
Status Output
Modbus RS-485
PFRN Controller Network
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Port 1
Port 2
Start In
12-24 VDC, 50mA max
Status Out
N.O.
0-120 VAC/DC, 80mA max
12-24 VDC
+ Vin -
1
2
3
6.3A
Fuse
Safety
Input/
Terminal
Rated
Output
1 Vin +
I
No
2 Vin -
3 EGND
GND
4 Signal In
-
5 PWR Out
Not Used
6 N.O. A
-
7 N.O. B
8 D+
9 D-
No
I/O
RS-485
10
GND
Port 1
I/O
Port 2
I/O
Yes
Port 3
I/O
Port 4
I/O
No-Term
Term
Port 3
Port 4
PF3107-00
Modbus Comm Module
v1.3
Spare
Electrical Ratings
12-24 V
DC
6.3A maximum
*Fused at 6.3A
RS-485, -6V – 6V Common Mode Range with reference to terminal
10 (RS-485 GND)
36 V
DC
1A maximum
PF3100 Product Manual
8 9 10
Tx Rx
Modbus
RS-485
Reset
PF3107-00
XX:00:00:00:XX:XX
139750
2021-12-31
v1.3.x
DOC-001149 v8.0
65