14.3 CONNECTION DIAGRAMS

Caution: Electrical devices connected to the controller must meet local electrical codes and be within
!
the voltage limits specified in this manual.
!
Caution: All field wiring must be properly fused and sized in accordance with local codes.
Caution: Wires must be installed such that the connection does not rely on the structural integrity of
!
the wire insulation and no more than one conductor is terminated in a single terminal.
14.3.1 POWER INPUT WIRING
PF3101-00 BMS Controller Card
12-24 VDC
1
-
Common
2
-
Earth GND
3
-
4
-
5
-
14.3.2 DIGITAL INPUT – DRY CONTACT
PF3101-00 BMS Controller Card
24
-
Pressure-
25
-
Pressure+
26
-
Level-
27
-
Level+
14.3.3 DIGITAL INPUT – WET CONTACT
PF3101-00 BMS Controller Card
12-24 VDC
1
-
Common
2
-
3
-
Earth GND
4
-
5
-
24
-
Pressure-
25
-
Pressure+
26
-
Level-
27
-
Level+
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Installation Notes:
Note 1
1. The power supply must be fused in accordance with local
+
-
2. Power input wiring is shown for the BMS Controller card
GND
DC Power
Supply
Installation Notes:
1. Pressure input wiring shown as an example only. Device
can be wired to other digital inputs in the same way. For I/O
Expansion inputs, the PWR Out terminal corresponds to the
NO
"+" terminal in the diagram and the Signal In terminal
C
corresponds to the "-" terminal in the diagram.
NC
2. The PF3100 system uses energized-to-run logic for all digital
Digital Input Switch
inputs. Wire to NO or NC contacts accordingly.
3. BMS: + terminal output matches system voltage input.
I/O Expansion – 12V Mode: PWR output is 14V
I/O Expansion – 24V Mode: PWR output is 24V
Ion Pilot Aux In - + terminal output is 12V
Installation Notes:
1. Pressure input wiring shown as an example only. Device
-
+
External DC Power
Source
2. The PF3100 system uses energized-to-run logic for all
3. External power source must be Earth grounded.
4. External power source must not (1) exceed 30V
C
NO
NC
Digital Input Switch
electrical codes.
as an example only. The power input to the Modbus,
Network and Pilot Spark cards can be wired in the same
way.
can be wired to other digital inputs in the same way. For
I/O Expansion inputs, the PWR Out terminal corresponds
to the "+" terminal in the diagram and the Signal In
terminal corresponds to the "-" terminal in the diagram.
digital inputs. Wire to NO or NC contacts accordingly.
drop below -0.5V with reference to BMS Controller card
Common terminal (terminal 2).