12.6 PFRN PORT

12.6.1 DETAILS
Terminals
Name
Type
12.6.2 INTENDED FIELD DEVICE CONNECTIONS
Field Device
PF3101-00 BMS card PFRN I/O
Network port
12.6.3 SYSTEM BEHAVIOR – DIAGNOSTIC LEDS
Name
Color
LED Behavior
Off
Pwr
Blue
On – Solid
On – Flickering
Off/flickering
Link
Green
On – Solid
12.6.4 SYSTEM BEHAVIOR UPON COMMUNICATION LOSS
Refer to
BMS PFRN I/O Network System Behavior
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
20
PFRN
PFRN I/O Network Port
Configuration Requirements
N/A
Interpretation
Port has no power
Port has power
Port has intermittent power
Port is not communicating
Port is communicating normally
for behavior under communication loss conditions.
6
7
8
9 10 11 12 13
Earth GND
5
4
N.O. Dry
Contact
3
Ou t
2
N.C. Dry
Contact
1
Ou t
SPST 120 VAC/DC, 80mA max
PF3113-00
IO Expansion Card
V2.0
Connection Diagrams
PFRN Connector Wiring
I/O Card PFRN Wiring Options
Issue/Corrective Action
No BMS Power – Make sure BMS Controller card is
powered on.
Wiring fault – Check PFRN wire terminations at BMS
and I/O Expansion card.
Hardware fault –
Contact Profire
N/A
Wiring fault – Check PFRN wire terminations at BMS
and I/O Expansion card.
Hardware fault –
Contact Profire
No PFRN Communication – Cycle power to BMS card
and check PFRN wire terminations at BMS and I/O
Expansion card.
N/A
PF3100 Product Manual
DOC-001149 v8.0
Signal Out Termination
Ground
Floating
14 15 16 17 18 19
1 2 3 4
Input #
6
7
8 9 10
11 12 13
14 15 16
17 18 19
4-20mA
Input 1
Input 2
Input 3
Input 4
Ou t
12V
24V
PF3113-00
PWR Out
XX:00:00:00:XX:XX
Mode
139750
Reset
2021-12-31
v2.0.x
20 - PFRN
for replacement.
for replacement.
83