13.7 PROVEN PRE-PURGE SEQUENCE

The Proven Pre-Purge sequence is a collection of sub-states that ensures a proper pre-purge for all forced draft
heating applications. The safety outputs are held de-energized through all the Proven Pre-Purge sub-states. The
sub-states are detailed in the sections below:
13.7.1 REQUEST PURGE POSITION STATE
The controller transitions to the Request Purge Position sub-state to ensure that all FARC channel outputs are
driven to their respective Purge Positions before initiating a pre-purge. All safety outputs are held de-energized
for the duration of the Request Purge Position sub-state.
13.7.1.1
SAFETY OUTPUT BEHAVIOR – REQUEST PURGE POSITION STATE
Card
PF3101-00 BMS Controller card
PF3102-00 Ion Pilot card
PF3102-01 UV Pilot card
13.7.1.2
TRANSITIONS TO THE REQUEST PURGE POSITION STATE
From
Scenario
Startup Checks
Absence of airflow proven
13.7.1.3
TRANSITIONS FROM THE REQUEST PURGE POSITION STATE
To
Scenario
Any
Lockout
Controller stopped by user
Purge position not proven
Waiting
Any
Prove Airflow
Purge position proven
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Startup Checks
Proven Pre-Purge
Request Purge Position
Prove A irflow
Pre-Purge
Request Pilot Position
Output
Pilot
SSV1
SSV2
Valve
Coil
Ignition Enable
Condition
No alarm or wait conditions present
Condition
Alarm condition present
Any
Any
Wait condition present
No alarm or wait conditions present
PF3100 Product Manual
Lockout
Waiting
Ignition
Output State
De-energized
De-energized
De-energized
De-energized
De-energized
Open
DOC-001149 v8.0
93