Code
Alert Name
UI/Modbus
1031
32
Invalid Configuration
1032
33
Ignition Switch Stuck
1033
34
Auxiliary Temperature High ESD
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Each of the conditions in the following list cause this alarm. Pressing the
OK button on the alert text opens a dialog with additional troubleshooting
information:
High Temp Setpoint Error:
High Temp SP below Pilot Off SP (If Pilot off Mode = Pilot off at SP)
1.
High Temp SP below Low Fire SP (If Low Fire setting is enabled)
2.
High Temp SP below Process Temp SP
3.
Pilot Off Setpoint Error:
Pilot off SP below Low Fire SP (If Low Fire setting is enabled)
4.
Pilot off SP below Process Temp SP
5.
Low Fire Setpoint Error:
Low Fire SP below Process Temp SP + 1
6.
Process SP Error:
Process Temp SP below 0
7.
Main Flame Config Error
Pilot Off Mode set to Off After Main On and Main Flame Detect is
8.
Disabled.
Level/Flow Setpoint Error:
Level/Flow High SP below Low SP + Deadband (when in 4-20 mode)
9.
Level/Flow Low SP below Deadband (when in 4-20 mode)
10.
Pressure Setpoint Error:
Pressure High SP below Low SP + Deadband (when in 4-20 mode)
11.
Pressure Low SP below Deadband (when in 4-20 mode)
12.
Appliance Configuration Error:
Minimum Controllers Running setting is greater than the number of
13.
controllers in the appliance
Proof of Airflow Configuration Error:
Proof of Airflow is enabled and HFV Mode setting is not set to Forced
14.
Draft or Purge Fan
HFV Mode setting is set to Forced Draft or Purge Fan and Proof of
15.
Airflow is not enabled
PID Configuration Error:
4-20 Aux Out Mode setting is set to PID Control or Appliance Firing
16.
Rate and Low Fire is disabled
Incinerator Configuration Error:
Waste Gas Off SP is above Pilot Off SP
17.
Assist Gas Off SP is above Waste Gas Off SP minus Waste Gas Off
18.
Deadband
Waste Gas On SP is above Assist Gas Off SP minus Assist Gas Off
19.
Deadband
Process Temp SP is above Assist Gas Off SP
20.
Process Temp SP is below Waste Gas On SP.
21.
The BMS Controller Ignition Switch input is stuck in the Start position.
Auxiliary temperature input reading is above its High Temp SP setting.