5.1

TERMINAL RATINGS

Safety
Name
Rated
Power Input
No
Relay Output
No
HFV
No
SSV2
Yes
SSV1
Yes
Pilot
Yes
Aux Out
No
Start
Yes
POC
Yes
Aux In
Yes
ESD
Yes
Pressure
Yes
Level
Yes
PFRN
Controller
Yes
Network
PFRN I/O
Yes
Network
Ignition Switch Yes
Keypad
No
License Key
No
1
The combined current requirements of the Start, POC, Aux In and ESD input devices cannot exceed 100mA.
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Terminal
Input/Output Electrical Ratings
1
12-24 VDC
I
2
Common
3
Earth GND
GND
4
STATUS A
-
5
STATUS B
6
-
O
7
+
8
-
O
9
+
10
-
O
11
+
12
-
O
13
+
14
-
O
15
+
16
-
I
17
+
O
18
-
I
19
+
O
20
-
I
21
+
O
22
-
I
23
+
O
24
-
I
25
+
O
26
-
I
27
+
O
28
I/O
29
I/O
30
I/O
31
I/O
32
I/O
Run
I
33
Ignite
I
On
O
34
O
35
I
12-24 V
DC
10A maximum
*Fused at 10A
Dry contact
120 V
/V
AC
DC
80mA maximum
12-24 V
DC
2A maximum
Pulsed Output with configurable PWM
Expected Load: Inductive/Resistive
12-24 V
DC
20mA maximum
Maximum output device impedance:
12V Mode: 250Ω, 24V Mode: 900Ω
30 V
max, 2mA minimum wetting current
DC
12-24 V
, 100mA maximum
DC
30 V
max, 2mA minimum wetting current
DC
12-24 V
, 100mA maximum
DC
30 V
max, 2mA minimum wetting current
DC
12-24 V
, 100mA maximum
DC
30 V
max, 2mA minimum wetting current
DC
12-24 V
, 100mA maximum
DC
Digital Mode: 30 V
max, 2mA minimum wetting current
DC
4-20 Mode: 30 V
max, 25mA maximum
DC
Input resistance ~200Ω
12-24 V
, 50mA maximum,
DC
Digital Mode: 30 V
max, 2mA minimum wetting current
DC
4-20 Mode: 30 V
max, 25mA maximum
DC
Input resistance ~200Ω
12-24 V
, 50mA maximum,
DC
36 V
DC
1A maximum
36 V
DC
1A maximum
3.3 V
DC
3.3 V
DC
3.3 V
DC
3.3 V
DC