13.11.2 INCINERATE STATE
13.11.2.1
SAFETY OUTPUT BEHAVIOR - INCINERATE STATE
Card
PF3101-00 BMS Controller card
PF3102-00 Ion Pilot card
PF3102-01 UV Pilot card
1
De-energized when Pilot Off Mode is set to Off After Main On
2
Energized under reignition conditions in accordance with configured Pilot Relight Mode and Pilot Relight Timeout settings
(Controller Settings > Outputs > Ignition).
13.11.2.2
TRANSITIONS TO THE INCINERATE STATE
From
Scenario
Process temperature is above its configured
Low Fire
Waste Gas On setpoint
Incinerate
Process temperature is below its configured
No Assist
Assist Gas Off Setpoint
13.11.2.3
TRANSITIONS FROM THE INCINERATE STATE
To
Scenario
Any
Lockout
Controller stopped by user
Flame loss
Any
Waiting
Any
Flame loss
Pilot
Any
Process temperature is below its configured
Low Fire
Waste Gas On setpoint
Incinerate
Process temperature is above its configured
No Assist
Assist Gas Off Setpoint
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Output
Pilot
SSV1
SSV2
Valve
Coil
Ignition Enable
Condition
Incinerator Enable setting is set to Enabled, AND
No alarm or wait or main permissive conditions present
No alarm or wait or main permissive conditions present
Condition
Alarm condition present
Any
Relight Attempts setting has been exceeded
Wait condition present
Main permissive condition present, AND
Pilot Off Mode setting is set to Off after Main On or Follow
Main
Relight Attempts setting has not been exceeded
Main permissive condition present, AND
Pilot Off Mode setting is set to Disabled or Off at Setpoint
Incinerator Enable setting is set to Enabled, AND
No alarm or wait or main permissive conditions present
No alarm or wait or main permissive conditions present
PF3100 Product Manual
DOC-001149 v8.0
Output State
Energized
1
Energized
Energized
Energized
1
De-energized
2
Open
2
104

Advertisement

Table of Contents
loading

Table of Contents